Onset HOBO CTV-E

HOBO CTV 60-600 Amp AC Split-Core Current Sensor Transformer

Regular price£252.95 Inc VAT Price on application
£210.79 ex VAT @ 20%
/
Shipping calculated at checkout.
SKU CTV-E
  • In stock, only 1 left
  • Available to order

A split-core sensor to record AC amperage of 60 to 600 amps AC. For use with Onset HOBO external-channel data loggers.

Input AC current, sine wave, single phase 50 to 60 Hz, load power factor 0.5 to 1.0 lead or lag.

HousingSplit-Core
Compatible WithFor use with HOBO U12, UX120-006M, MX1100, and ZW series external-channel data loggers.
MeasurementsCurrent AC

The country of origin for this product is the United States.

Range: 60 to 600 amps
Accuracy with H8: ±5.0% of full scale
Accuracy with U12: ±4.5% of full scale
Accuracy with UX120-006M, MX1104 and MX1105: ±2.1% of full scale
Response time (from 10% to 90% of amplitude): see table
Input current: AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag
Voltage rating: 600 VAC
Construction and operating environment: Molded plastic housing for indoor use per UL508; pivoting leg (leg on CTV-D and CTV-E units is fully removable); UL listed.
Cable length: 1.8m cable (6 foot)
Dimensions: see table

Part No. Range (Amps AC) Approximate Response Time (milliseconds) Dimensions
Window Outer Length Outer Width Height
CTV-A 2–20 440 2.8 cm x 2.3 cm 1.1 in. x 0.9 in. 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-B 5–50 200 2.8 cm x 2.3 cm 1.1 in. x 0.9 in 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-C 10–100 100 2.8 cm x 2.3 cm 1.1 in. x 0.9 in 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-D 20–200 450 3.8 cm x 3.3 cm 1.5 in. x 1.3 in 9.9 cm 3.9 in 11.9 cm 4.7 in 2.8 cm 1.1 in
CTV-E 60–600 490 7.4 cm x 6.4 cm 2.9 in. x 2.5 in 13.5 cm 5.3 in 15.0 cm 5.9 in 2.8 cm 1.1 in

This item is priced on application. Tell us what you need and we'll send you a quote.

Or call us on 01243 558270

BUYING IN BULK, OR JUST WANT SOME HELPFUL ADVICE?

Call +44 (0)1243 558270, or fill out our contact form.

Key Features

  • UL listed
  • Sensor power induced from line voltage
  • Self-gripping split-core design for fast installation.

This split-core sensor records AC amperage; for use with HOBO U12, UX120-006M, MX1100, and ZW series external-channel data loggers. With an input of AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag.

Compatible with: