Onset HOBO CTV-C

HOBO CTV 10-100 Amp AC Split-Core Current Sensor Transformer

Regular price£204.95 Inc VAT Price on application
£170.79 ex VAT @ 20%
/
Shipping calculated at checkout.
SKU CTV-C
  • In stock, only 3 left
  • Available to order

A split-core sensor to record AC amperage of 10 to 100 amps AC. For use with Onset HOBO external-channel data loggers.

Input AC current, sine wave, single phase 50 to 60 Hz, load power factor 0.5 to 1.0 lead or lag.

Range10 - 100 AAC
HousingSplit-Core
Compatible WithFor use with HOBO U12, UX120-006M, MX1100, and ZW series external-channel data loggers
MeasurementsCurrent AC

The country of origin for this product is the United States.

Range: 10 to 100 Amps
Accuracy with H8: ±5.0% of full scale
Accuracy with U12: ±4.5% of full scale
Accuracy with UX120-006M, MX1104 and MX1105: ±2.1% of full scale
Response time (from 10% to 90% of amplitude): see table
Input current: AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag
Voltage rating: 600 VAC
Construction and operating environment: Molded plastic housing for indoor use per UL508; pivoting leg (leg on CTV-D and CTV-E units is fully removable); UL listed.
Cable length: 1.8m cable (6 foot)
Dimensions: see table

Part No. Range (Amps AC) Approximate Response Time (milliseconds) Dimensions
Window Outer Length Outer Width Height
CTV-A 2–20 440 2.8 cm x 2.3 cm 1.1 in. x 0.9 in. 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-B 5–50 200 2.8 cm x 2.3 cm 1.1 in. x 0.9 in 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-C 10–100 100 2.8 cm x 2.3 cm 1.1 in. x 0.9 in 7.4 cm 2.9 in 6.6 cm 2.6 in 2.5 cm 1.0 in
CTV-D 20–200 450 3.8 cm x 3.3 cm 1.5 in. x 1.3 in 9.9 cm 3.9 in 11.9 cm 4.7 in 2.8 cm 1.1 in
CTV-E 60–600 490 7.4 cm x 6.4 cm 2.9 in. x 2.5 in 13.5 cm 5.3 in 15.0 cm 5.9 in 2.8 cm 1.1 in

This item is priced on application. Tell us what you need and we'll send you a quote.

Need a quick answer? Use live chat. For quotes or detailed requirements, send us the details and we'll reply by email.

Or call us on 01243 558270

Buying in Volume, or Just Want Some Helpful Advice?

Call +44 (0)1243 558270, or fill out our contact form.

Key Features

  • UL listed
  • Sensor power induced from line voltage
  • Self-gripping split-core design for fast installation.

This split-core sensor records AC amperage; for use with HOBO U12, UX120-006M, MX1100, and ZW series external-channel data loggers. With an input of AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag.

Compatible with: